6-3 REMOTE CONTROLLER
06-05
Remote controller address
Ex. Self-diagnosis
Error code
SU MO TU WE TH FR SA
If there is a problem with the air conditioner, it will
stop running and " E:EE " will be displayed instead
of the clock.
Error code displayed on wired or simple remote controller
6-3-1 WIRED REMOTE CONTROLLER
6-3-2 SIMPLE REMOTE CONTROLLER
DAY OFF
DELETE
SET
ENERGY
SAVE
SET BACK
DAY
CLOCK ADJUST
Display
DAY OFF
DELETE
SET
ENERGY
SAVE
SET BACK
DAY
CLOCK ADJUST
SET
(1) Stop the air conditioner operation.
(2) Press the Set Temperature buttons and at the same time
for more than 5 seconds to start the self-diagnosis.
(3)Press the Set Temperature buttons and at the same time
for more than 5 seconds to stop the self-diagnosis.
.
SET
Error Code
Remote controller
address
If there is a problem with the air conditioner it will stop
running and " EE:EE " will be displayed.
(1) If the operation lamp is on then press
button to turn it off.
(2) Press the
and the
buttons at the same time
for more than three seconds to start the self diagnosis
check.
An error code will be displayed display area.
(3) Press the
and the
buttons again for more than
three seconds to end the self diagnosis check.
Error code history can be displayed. Please refer to
"Installation Instruction Sheet" of the remote controller.
SU MO TU WE TH FR SA
Error cord
E : 00
Error contents
E : 06
E : 02
E : 04
E : 07
E : 09
E : 0A
E : 0b
E : 0C
No error
Model information abnormal
Power supply frequency abnormal
EEPROM access error
EEPROM deletion error
Room temperature thermistor error
Indoor unit heat exchanger thermistor (middle) error
Indoor unit heat exchanger thermistor (inlet) error
Indoor unit heat exchanger thermistor (outlet) error
E : 0d
E : 11
E : 12
E : 13
E : 1F
E : 21
Blower temperature thermistor error
Drain abnormal
Room temperature abnormal
indoor unit fan error
Transmission error
Parallel communication error
E : 32
Outdoor unit error
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...