Trouble shooting 22
OUTDOOR UNIT
OUTDOOR UNIT
Error Method:
Error Method:
OUTDOOR TEMPERATURE
THERMISTOR ABNORMAL
Check Point 2 : Remove CN26, measure the thermistor resistance
Check Point 2 : Remove CN26, measure the thermistor resistance
If its open or short, replace the thermistor and turn on the main power.
8.0
30
12.5
20
15.8
15
5.3
40
20.2
25.9
33.6
44.0
58.2
105
Resistance Value ( )
k
k
10
5
0
-5
-10
-20
Temperature ( )
1.8
2.5
3.6
Resistance Value ( )
70
60
50
Temperature ( )
P/No.
9703516078
(Outdoor temperature thermistor)
Check Point 3 : Check control PCB CN26 Voltage DC 5.0V
Check Point 3 : Check control PCB CN26 Voltage DC 5.0V
If CN26 voltage can not be measured, replace Control PCB.
Thermistor characteristics (Approx)
Check Point 1 :
Check Point 1 :
Checking wiring of Connector CN25
Checking wiring of Connector CN25
Loose connector
Incorrect wiring
Thermistor cable is cut off
When reworking on the loose connector, erroneous connection, keep the power shut off.
Indicate or Display:
Indicate or Display:
Indoor Unit :
Operation LED
Flash
Flash
,
,
Timer LED
3 Times Blink
3 Times Blink
Swing LED
3 Times Blink
3 Times Blink
Outdoor Unit :
LED1
Flash
Flash
,
,
LED3
11
11
Times Blink
Times Blink
ERROR CODE: E:32
Detective Actuators:
Detective Actuators:
Outdoor temperature thermistor
Open or Short
Detective details:
Detective details:
When thermistor open or short detected during the compressor is in
operation, the compressor stops, indicates error and output the error
information to the network.
Forecast of Cause
Forecast of Cause:
1. Connector wiring defective
2. Thermistor defective
3. Control PCB defective
06-26
HEX OUTLET TEMP THERMISTOR
HEX CENTER TEMP THERMISTOR
DC5V
CN21
CN22
CN24
CN25
CN26
YELLOW
BLUE
RED
RED
1
2
1
2
1
2
1
2
1
2
BROWN
BROWN
BLUE
BLUE
GREEN
GREEN
BLACK
BLACK
BLACK
BLACK
DISCHARGED TEMP THERMISTOR
SUCTION TEMP THERMISTOR
OUTDOOR TEMP THERMISTOR
Summary of Contents for AO54FJ
Page 5: ...1 TEST RUN TM SERIES R410A ...
Page 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Page 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Page 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Page 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Page 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Page 128: ...7 INSTALLATION TM SERIES R410A ...
Page 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Page 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Page 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Page 157: ...MODELS AR36 AR45 09 08 ...
Page 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Page 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Page 160: ...MODELS AU36 AU45 AU54 09 11 ...
Page 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Page 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Page 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...