Name
Type
Description
U2LOW
BOOLEAN
Loss of U2 voltage
UL1DIFF
REAL
Differential Voltage phase L1
UL2DIFF
REAL
Differential Voltage phase L2
UL3DIFF
REAL
Differential Voltage phase L3
9.5.5
Settings
Table 293:
VDCPTOV Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
BlkDiffAtULow
No
Yes
-
-
Yes
Block operation at low voltage
UDTrip
2.0 - 100.0
%UB
0.1
5.0
Operate level, in % of UBase
tTrip
0.000 - 60.000
s
0.001
1.000
Time delay for voltage differential operate,
in seconds
tReset
0.000 - 60.000
s
0.001
0.000
Time delay for voltage differential reset, in
seconds
UDAlarm
2.0 - 100.0
%UB
0.1
2.0
Alarm level, in % of UBase
tAlarm
0.000 - 60.000
s
0.001
2.000
Time delay for voltage differential alarm,
in seconds
U1Low
1.0 - 100.0
%UB
0.1
70.0
Input 1 undervoltage level, in % of UBase
U2Low
1.0 - 100.0
%UB
0.1
70.0
Input 2 undervoltage level, in % of UBase
tBlock
0.000 - 60.000
s
0.001
0.000
Reset time for undervoltage block
Table 294:
VDCPTOV Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
RFL1
0.000 - 3.000
-
0.001
1.000
Ratio compensation factor phase L1
U2L1*RFL1=U1L1
RFL2
0.000 - 3.000
-
0.001
1.000
Ratio compensation factor phase L2
U2L2*RFL2=U1L2
RFL3
0.000 - 3.000
-
0.001
1.000
Ratio compensation factor phase L3
U2L3*RFL3=U1L3
Table 295:
VDCPTOV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
1MRK502052-UEN B
Section 9
Voltage protection
529
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...