16.3.5
Settings
Table 655:
SSIML Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
LevelAlmLimit
1.00 - 100.00
-
0.01
5.00
Alarm setting for level
LevelLOLimit
1.00 - 100.00
-
0.01
3.00
Level lockout setting
TempAlarmLimit
-40.00 - 200.00
-
0.01
30.00
Temperature alarm level setting of the
medium
TempLOLimit
-40.00 - 200.00
-
0.01
30.00
Temperature lockout level of the medium
tLevelAlarm
0.000 - 60.000
s
0.001
0.000
Time delay for level alarm
tLevelLockOut
0.000 - 60.000
s
0.001
0.000
Time delay for level lockout indication
tTempAlarm
0.000 - 60.000
s
0.001
0.000
Time delay for temperature alarm
tTempLockOut
0.000 - 60.000
s
0.001
0.000
Time delay for temperture lockout
tResetLevelAlm
0.000 - 60.000
s
0.001
0.000
Reset time delay for level alarm
tResetLevelLO
0.000 - 60.000
s
0.001
0.000
Reset time delay for level lockout
tResetTempLO
0.000 - 60.000
s
0.001
0.000
Reset time delay for temperture lockout
tResetTempAlm
0.000 - 60.000
s
0.001
0.000
Reset time delay for temperture alarm
16.3.6
Operation principle
Liquid medium supervision SSIML is used to monitor the oil level in the circuit
breaker. Binary inputs of oil level LVL_ALM, LEVEL_LO and oil level signal
LEVEL are taken into account to initiate the alarms LVL_ALM and LVL_LO. When
LEVEL is less than
LevelAlmLimit
or binary signal from CB LVL_ALM is high, then
the oil level indication alarm, LVL_ALM will be initiated. Similarly, if oil level input
LEVEL is less than
LevelLOLimit
or binary signal from CB LVL_LO is high or
temperature input TEMP is above lockout level
TempLOLimit
, then the oil level
indication lockout, LVL_LO will be initiated.
There may be sudden change in oil level for a very small time, for which the function
need not to initiate any alarm. That is why two time delays
tLevelAlarm
or
tLevelLockOut
have been included. If the oil level goes below the settings for more
than these time delays, then only the corresponding alarm LVL_ALM or lockout
LVL_LO will be initiated. The SET_L_LO binary input is used for setting the gas
pressure lockout. The LVL_LO output retains the last value until it is reset by using
the binary input RESET_LO. Hysteresis type comparators have been used with the
setting for relative and absolute hysteresis. The binary input BLK_ALM can be used
for blocking the alarms, and the BLOCK input can block both alarms and the lockout
indication.
Temperature of the medium is available from the input signal of temperature. The
signal is monitored to detect high temperature.
1MRK502052-UEN B
Section 16
Monitoring
895
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...