The RD inverse curve gives a logarithmic delay, as used in the Combiflex protection
RXIDG. The curve enables a high degree of selectivity required for sensitive residual
earth-fault current protection, with ability to detect high-resistive earth faults. The
curve is described by equation
[ ] 5.8 1.35 ln
=
-
×
× >
æ
ö
ç
÷
è
ø
i
t s
k in
EQUATION1195 V1 EN
(Equation 163)
where:
in>
is the set start current for step n,
k
is set time multiplier for step n and
i
is the measured current
If the curve type programmable is chosen, the user can make a tailor made inverse time
curve according to the general equation
[ ]
=
+
×
-
>
æ
ö
ç
÷
ç
÷
ç
÷
æ
ö
ç
÷
ç
÷
è
ø
è
ø
p
A
t s
B k
i
C
in
EQUATION1196 V1 EN
(Equation 164)
Also the reset time of the delayed function can be controlled. There is the possibility
to choose between three different reset time-lags.
•
Instantaneous Reset
•
IEC Reset
•
ANSI Reset.
If instantaneous reset is chosen the timer will be reset directly when the current drops
below the set start current level minus the hysteresis.
If IEC reset is chosen the timer will be reset after a set constant time when the current
drops below the set start current level minus the hysteresis.
If ANSI reset time is chosen the reset time will be dependent of the current after fault
clearance (when the current drops below the start current level minus the hysteresis).
The timer will reset according to equation
1MRK502052-UEN B
Section 25
Inverse time characteristics
1251
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...