8.8.8
Technical data
Table 206:
CCRBRF technical data
Function
Range or value
Accuracy
Operate phase
current
(5-200)% of
lBase
±1.0% of I
r
at I
£
I
r
±1.0% of I at I > I
r
Reset ratio, phase
current
> 95%
-
Operate residual
current
(2-200)% of
lBase
±1.0% of I
r
at I
£
I
r
±1.0% of I at I > I
r
Reset ratio, residual
current
> 95%
-
Phase current level
for blocking of
contact function
(5-200)% of
lBase
±1.0% of I
r
at I
£
I
r
±1.0% of I at I > I
r
Reset ratio
> 95%
-
Operate time for
current detection
10 ms typically
-
Reset time for current
detection
15 ms maximum
-
Time delay for re-trip
at 0 to 2 x I
set
(0.000-60.000) s
±0.2% or ±15 ms whichever is
greater
Time delay for back-
up trip at 0 to 2 x I
set
(0.000-60.000) s
±0.2% or ±15 ms whichever is
greater
Time delay for back-
up trip at multi-phase
start at 0 to 2 x I
set
(0.000-60.000) s
±0.2% or ±20 ms whichever is
greater
Additional time delay
for a second back-up
trip at 0 to 2 x I
set
(0.000-60.000) s
±0.2% or ±20 ms whichever is
greater
Time delay for alarm
for faulty circuit
breaker
(0.000-60.000) s
±0.2% or ±15 ms whichever is
greater
8.9
Pole discordance protection CCPDSC
8.9.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Pole discordance protection
CCPDSC
PD
SYMBOL-S V1 EN
52PD
1MRK502052-UEN B
Section 8
Current protection
413
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...