19.2
Transmission of analog data from LDCM
LDCMTransmit
19.2.1
Function block
LDCMTRN
^CT1L1
^CT1L2
^CT1L3
^CT1N
^CT2L1
^CT2L2
^CT2L3
^CT2N
IEC10000017-1-en.vsd
IEC10000017 V1 EN
Figure 495:
LDCMTransmit function block
The function blocks are not represented in the Application
Configuration tool except for the LDCMTRN function block that is
visible in ACT. The signals appear only in the Signal Matrix tool when
a LDCM is included in the configuration with the function selector
tool.
19.2.2
Signals
Table 824:
LDCMTRN Input signals
Name
Type
Default
Description
CT1L1
STRING
0
Input to be used for transmit CT-group1 line L1 to
remote end
CT1L2
STRING
0
Input to be used for transmit CT-group1 line L2 to
remote end
CT1L3
STRING
0
Input to be used for transmit CT-group1 line L3 to
remote end
CT1N
STRING
0
Input to be used for transmit CT-group1 neutral N to
remote end
CT2L1
STRING
0
Input to be used for transmit CT-group2 line L1 to
remote end
CT2L2
STRING
0
Input to be used for transmit CT-group2 line L2 to
remote end
CT2L3
STRING
0
Input to be used for transmit CT-group2 line L3 to
remote end
CT2N
STRING
0
Input to be used for transmit CT-group2 neutral N to
remote end
1MRK502052-UEN B
Section 19
Remote communication
1087
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...