16.9.4
Function block
L4UFCNT
BLOCK
INPUT
RESET
ERROR
OVERFLOW
LIMIT1
LIMIT2
LIMIT3
LIMIT4
VALUE
IEC12000029-1-en.vsd
IEC12000029 V1 EN
Figure 452:
L4UFCNT function block
16.9.5
Signals
Table 705:
L4UFCNT Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
INPUT
BOOLEAN
0
Input for counter
RESET
BOOLEAN
0
Reset of function
Table 706:
L4UFCNT Output signals
Name
Type
Description
ERROR
BOOLEAN
Error indication on counter limit and/or initial value
settings
OVERFLOW
BOOLEAN
Overflow indication on count of greater than
MaxValue
LIMIT1
BOOLEAN
Counted value is larger than or equal to
CounterLimit1
LIMIT2
BOOLEAN
Counted value is larger than or equal to
CounterLimit2
LIMIT3
BOOLEAN
Counted value is larger than or equal to
CounterLimit3
LIMIT4
BOOLEAN
Counted value is larger than or equal to
CounterLimit4
VALUE
INTEGER
Counted value