Name
Values (Range)
Unit
Step
Default
Description
tSelectTimeout
1.0 - 60.0
s
0.1
30.0
Select timeout
tBrokenConTout
0 - 3600
s
1
0
Broken connection timeout
tKeepAliveT
0 - 3600
s
1
10
Keep-Alive timer
Table 478:
MST2TCP Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
SlaveAddress
0 - 65519
-
1
1
Slave address
MasterAddres
0 - 65519
-
1
1
Master address
ValMasterAddr
No
Yes
-
-
Yes
Validate source (master) address
MasterIP-Addr
0 - 18
IP
Address
1
0.0.0.0
Master IP-address
MasterIPNetMsk
0 - 18
IP
Address
1
255.255.255.255
Master IP net mask
Obj1DefVar
1:BISingleBit
2:BIWithStatus
-
-
1:BISingleBit
Object 1, default variation
Obj2DefVar
1:BIChWithoutTim
e
2:BIChWithTime
3:BIChWithRelTim
e
-
-
3:BIChWithRelTim
e
Object 2, default variation
Obj3DefVar
1:DIWithoutFlag
2:DIWithFlag
-
-
1:DIWithoutFlag
Object 3, default variation
Obj4DefVar
1:DIChWithoutTim
e
2:DIChWithTime
3:DIChWithRelTim
e
-
-
3:DIChWithRelTim
e
Object 4, default variation
Obj10DefVar
1:BO
2:BOStatus
-
-
2:BOStatus
Object 10, default variation
Obj20DefVar
1:BinCnt32
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF
-
-
5:BinCnt32WoutF
Object 20, default variation
Table continues on next page
1MRK502052-UEN B
Section 14
Control
781
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...