Name
Type
Values (Range)
Unit
Description
BO12VALUE
BOOLEAN
1=1
0=0
-
Binary output 12 value
BO12FORCE
BOOLEAN
0=Normal
1=Forced
-
Binary output 12 force
BO12
BOOLEAN
0=Normal
1=Forced
2=Blocked
-
Binary output 12 status
21.2.10.6
Technical data
Table 911:
IOM - Binary input/output module
Quantity
Rated value
Nominal range
Binary inputs
8
-
DC voltage, RL
24/30 V
48/60 V
110/125 V
220/250 V
RL
±
20%
RL
±
20%
RL
±
20%
RL
±
20%
Power consumption
24/30 V, 50 mA
48/60 V, 50 mA
110/125 V, 50 mA
220/250 V, 50 mA
220/250 V, 110 mA
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
max. 0.5 W/input
-
Counter input frequency
10 pulses/s max
Oscillating signal discriminator
Blocking settable 1-40 Hz
Release settable 1-30 Hz
Debounce filter
Settable 1-20 ms
Maximum 176 binary input channels may be activated
simultaneously with influencing factors within nominal range.
Table 912:
IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity
Trip and signal relays
Fast signal relays (parallel reed
relay)
Binary outputs
10
2
Max system voltage
250 V AC, DC
250 V DC
Test voltage across open contact,
1 min
1000 V rms
800 V DC
Current carrying capacity
Per relay, continuous
Per relay, 1 s
Per process connector pin,
continuous
8 A
10 A
12 A
8 A
10 A
12 A
Table continues on next page
1MRK502052-UEN B
Section 21
IED hardware
1179
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...