Selected current
StartCurr_UC1
Operation_UC1=On
Bin input: BLKUC1
STUC1
en05000750.vsd
TRUC1
Bin input: BLKUC1TR
DEF
AND
AND
IEC05000750 V1 EN
Figure 281:
Simplified internal logic diagram for built-in first undercurrent step that is, UC1 (step UC2 has the
same internal logic)
a
b
a>b
Selected voltage
StartVolt_OV1
Operation_OV1=On
BLKOV1
Inverse time
selected
en05000751.vsd
Inverse
DEF
DEF time
selected
STOV1
TROV1
AND
BLKTROV1
AND
OR
IEC05000751 V1 EN
Figure 282:
Simplified internal logic diagram for built-in first overvoltage step OV1 (step OV2 has the same
internal logic)
Section 11
1MRK502052-UEN B
Multipurpose protection
590
Technical manual