18.6
IEC 60870-5-103 communication protocol
18.6.1
Introduction
IEC 60870-5-103 communication protocol is mainly used when a protection IED
communicates with a third party control or monitoring system. This system must have
software that can interpret the IEC 60870-5-103 communication messages.
18.6.2
Measurands for IEC 60870-5-103 I103MEAS
18.6.2.1
Functionality
103MEAS is a function block that reports all valid measuring types depending on
connected signals.
The set of connected input will control which ASDUs (Application Service Data
Units) are generated.
•
9
Will be generated if at least IL1 is connected. IL2, IL3, UL1, UL2, UL3, P, Q,
F are optional but there can be no holes.
•
3.4
Will be generated if IN and UN are present.
•
3.3
Will be generated if IL2, Ul1L2, P and Q present.
•
3.2
Will be generated if IL2, UL1L2 and P or Q missing.
•
3.1
Will be generated if IL2 present and IL1 missing (otherwise IL2 in 9).
Description for I103MEAS function block:
9 = IL1
3.4 = IN AND UN
3.3 = IL2 AND UL1L2 AND P AND Q
3.2 = IL2 AND UL1L2 AND NOT 3.3
3.1 = IL2 AND NOT (3.2 OR 3.3 OR 9)
18.6.2.2
Identification
Function description
Function block
name
IEC 60617
identification
ANSI/IEEE C37.2
device number
Measurands for IEC 60870-5-103
I103MEAS
-
-
Section 18
1MRK502052-UEN B
Station communication
1030
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...