Name
Values (Range)
Unit
Step
Default
Description
PLowLim
-2000.0 - 2000.0
%SB
0.1
-120.0
Low limit in % of SBase
PLowLowLim
-2000.0 - 2000.0
%SB
0.1
-150.0
Low Low limit in % of SBase
PLimHyst
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range (common
for all limits)
QDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
QZeroDb
0 - 100000
m%
1
500
Zero point clamping in 0,001% of range
QHiHiLim
-2000.0 - 2000.0
%SB
0.1
150.0
High High limit in % of SBase
QHiLim
-2000.0 - 2000.0
%SB
0.1
120.0
High limit in % of SBase
QLowLim
-2000.0 - 2000.0
%SB
0.1
-120.0
Low limit in % of SBase
QLowLowLim
-2000.0 - 2000.0
%SB
0.1
-150.0
Low Low limit in % of SBase
QLimHyst
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range (common
for all limits)
PFDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
PFZeroDb
0 - 100000
m%
1
500
Zero point clamping in 0,001% of range
PFHiHiLim
-1.000 - 1.000
-
0.001
1.000
High High limit (physical value)
PFHiLim
-1.000 - 1.000
-
0.001
0.800
High limit (physical value)
PFLowLim
-1.000 - 1.000
-
0.001
-0.800
Low limit (physical value)
PFLowLowLim
-1.000 - 1.000
-
0.001
-1.000
Low Low limit (physical value)
PFLimHyst
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range (common
for all limits)
UDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UZeroDb
0 - 100000
m%
1
500
Zero point clamping in 0,001% of range
UHiHiLim
0.0 - 200.0
%UB
0.1
150.0
High High limit in % of UBase
UHiLim
0.0 - 200.0
%UB
0.1
120.0
High limit in % of UBase
ULowLim
0.0 - 200.0
%UB
0.1
80.0
Low limit in % of UBase
ULowLowLim
0.0 - 200.0
%UB
0.1
60.0
Low Low limit in % of UBase
ULimHyst
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range (common
for all limits)
IDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
IZeroDb
0 - 100000
m%
1
500
Zero point clamping in 0,001% of range
IHiHiLim
0.0 - 500.0
%IB
0.1
150.0
High High limit in % of IBase
IHiLim
0.0 - 500.0
%IB
0.1
120.0
High limit in % of IBase
ILowLim
0.0 - 500.0
%IB
0.1
80.0
Low limit in % of IBase
ILowLowLim
0.0 - 500.0
%IB
0.1
60.0
Low Low limit in % of IBase
ILimHyst
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range (common
for all limits)
FrDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
FrZeroDb
0 - 100000
m%
1
500
Zero point clamping in 0,001% of range
Table continues on next page
Section 16
1MRK502052-UEN B
Monitoring
866
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...