13.3.8
Technical data
Table 361:
VDSPVC technical data
Function
Range or value
Accuracy
Operate value, block of main fuse
failure
(10.0-80.0)% of UBase
±0.5% of Ur
Reset ratio
<110%
Operate time, block of main fuse
failure at 1 to 0 x U
r
Min. = 5 ms
–
Max. = 15 ms
Reset time, block of main fuse
failure at 0 to 1 x U
r
Min. = 15 ms
–
Max. = 30 ms
Operate value, alarm for pilot
fuse failure
(10.0-80.0)% of UBase
±0.5% of Ur
Reset ratio
<110%
–
Operate time, alarm for pilot fuse
failure at 1 to 0 x U
r
Min. = 5 ms
–
Max. = 15 ms
Reset time, alarm for pilot fuse
failure at 0 to 1 x U
r
Min. = 15 ms
–
Max. = 30 ms
1MRK502052-UEN B
Section 13
Secondary system supervision
623
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...