When the maximum phase-to-phase voltage is larger than
DisarmU>
for the period
tDisarm
, it is ensured generator is on line. During this state, undervoltage operation is
disarmed, blocking the overcurrent operation and thus the function becomes
inoperative.
BLOCK input can be used to block AEGPVOC . In addition, the BLKTR input that
blocks the TRIP signal is also present. The input BLKTR can be used if AEGPVOC
is to be used only for monitoring purposes.
I>
Operation = ON
a
a>b
b
Imax_DFT
AND
BLOCK
TRIP
tOC
START
ARMED
S
R
NOUT
OUT
ArmU<
a
a<b
b
Uph-ph_max_DFT
t
tArm
ON - Delay
DisarmU>
a
a>b
b
t
tDisarm
ON - Delay
OR
AND
IEC09000784-2-en.vsd
t
IEC09000784 V2 EN
Figure 206:
AEGPVOC logic diagram
8.13.1.7
Technical data
Table 240:
AEGPVOC technical data
Function
Range or value
Accuracy
Operate value,
overcurrent
(5-900)% of IBase
±1.0% of I
r
at I≤I
r
±1.0% of I at I>I
r
Reset ratio, overcurrent >95% at (20–900)% of IBase
-
Transient overreach,
overcurrent function
<10% at τ = 100 ms
-
Critical impulse time,
overcurrent
10 ms typically at 0 to 2 x I
set
-
Impulse margin time,
overcurrent
15 ms typically
-
Operate value,
undervoltage
(2-150)% of UBase
±0.5% of U
r
at U ≤ U
r
±0.5% of U at U > U
r
Critical impulse time,
undervoltage
10 ms typically at 2 to 0 x U
set
-
Table continues on next page
1MRK502052-UEN B
Section 8
Current protection
445
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...