
current from the W2 side compensated for eventual power transformer phase shift and
transferred to the power transformer W1 side. These negative sequence current
contributions are phasors, which are further used in directional comparisons, to
characterize a fault as internal or external. See section
for more information.
The magnitudes of the negative sequence differential current expressed in the HV side
A can be read as service values from the function. In the same time it is available as
outputs IDNSMAG from the differential protection function block. Thus, it can be
connected to the disturbance recorder and automatically recorded during any external
or internal fault condition.
Internal/external fault discriminator
The internal/external fault discriminator is a very powerful and reliable
supplementary criterion to the traditional differential protection. It is recommended
that this feature shall be always used (that is,
On
) when protecting three-phase power
transformers. The internal/external fault discriminator detects even minor faults, with
a high sensitivity and at high speed, and at the same time discriminates with a high
degree of dependability between internal and external faults.
The internal/external fault discriminator responds to the magnitudes and the relative
phase angles of the negative-sequence fault currents at the different windings of the
protected power transformer. The negative sequence fault currents must first be
referred to the same phase reference side, and put to the same magnitude reference.
This is done by the matrix expression (see equation
).
Operation of the internal/external fault discriminator is based on the relative position
of the two phasors representing the winding one (W1) and winding two (W2) negative
sequence current contributions, respectively, defined by expression shown in
equation
. It performs a directional comparison between these two phasors. First,
the LV side phasor is referred to the HV side (W1 side): both the magnitude, and the
phase position are referred to the HV (W1 side). Then the relative phase displacement
between the two negative sequence current phasors is calculated. In case of three-
winding power transformers, a little more complex algorithm is applied, with two
directional tests. The overall directional characteristic of the internal/external fault
discriminator is shown in figure
, where the directional characteristic is defined by
two setting parameters:
1.
IMinNegSeq
2.
NegSeqROA
1MRK502052-UEN B
Section 6
Differential protection
127
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...