Another information element in ASDU23 is the FAN (fault number). According to the
standard this is a number that is incremented when a protection function takes action.
FAN is equal to disturbance number, which is incremented for each disturbance.
ASDU26 / ASDU31
When a disturbance has been selected by the master by sending ASDU24, the
protection equipment answers by sending ASDU26, which contains an information
element named NOF (number of grid faults). This number must indicate fault number
in the power system,that is, a fault in the power system with several trip and auto-
reclosing has the same NOF (while the FAN must be incremented). NOF is just as
FAN, equal to disturbance number.
Interoperability, physical layer
Supported
Electrical Interface
EIA RS-485
Yes
number of loads
32
Optical interface
glass fibre
Yes
plastic fibre
Transmission speed
9600 bit/s
Yes
19200 bit/s
Yes
Link Layer
DFC-bit used
Yes
Connectors
connector F-SMA
No
connector BFOC/2.5
Yes
Interoperability, application layer
Supported
Selection of standard ASDUs in monitoring direction
ASDU
Yes
1
Time-tagged message
Yes
2
Time-tagged message with rel. time
Yes
3
Measurands I
Yes
4
Time-tagged message with rel. time
Yes
5
Identification
Yes
6
Time synchronization
Yes
8
End of general interrogation
Yes
9
Measurands II
Yes
Table continues on next page
1MRK502052-UEN B
Section 18
Station communication
1059
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...