13.2.6
Monitored data
Table 353:
FUFSPVC Monitored data
Name
Type
Values (Range)
Unit
Description
3I0
REAL
-
A
Magnitude of zero
sequence current
3I2
REAL
-
A
Magnitude of negative
sequence current
3U0
REAL
-
kV
Magnitude of zero
sequence voltage
3U2
REAL
-
kV
Magnitude of negative
sequence voltage
13.2.7
Operation principle
13.2.7.1
Zero and negative sequence detection
The zero and negative sequence function continuously measures the currents and
voltages in all three phases and calculates, see figure
•
the zero-sequence voltage 3U0
•
the zero-sequence current 3I0
•
the negative sequence current 3I2
•
the negative sequence voltage 3U2
The measured signals are compared with their respective set values
3U0>
and
3I0<
,
3U2>
and
3I2<
.
The function enable the internal signal FuseFailDetZeroSeq if the measured zero-
sequence voltage is higher than the set value
3U0>
and the measured zero-sequence
current is below the set value
3I0<
.
The function enable the internal signal FuseFailDetNegSeq if the measured negative
sequence voltage is higher than the set value
3U2>
and the measured negative
sequence current is below the set value
3I2<
.
A drop out delay of 100 ms for the measured zero-sequence and negative sequence
current will prevent a false fuse failure detection at un-equal breaker opening at the
two line ends.
Section 13
1MRK502052-UEN B
Secondary system supervision
610
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...