14.2.8.5
Signals
Table 379:
BH_LINE_A Input signals
Name
Type
Default
Description
QA1_OP
BOOLEAN
0
QA1 is in open position
QA1_CL
BOOLEAN
0
QA1 is in closed position
QB6_OP
BOOLEAN
0
QB6 is in open position
QB6_CL
BOOLEAN
0
QB6 is in close position
QB1_OP
BOOLEAN
0
QB1 is in open position
QB1_CL
BOOLEAN
0
QB1 is in closed position
QC1_OP
BOOLEAN
0
QC1 is in open position
QC1_CL
BOOLEAN
0
QC1 is in closed position
QC2_OP
BOOLEAN
0
QC2 is in open position
QC2_CL
BOOLEAN
0
QC2 is in closed position
QC3_OP
BOOLEAN
0
QC3 is in open position
QC3_CL
BOOLEAN
0
QC3 is in closed position
QB9_OP
BOOLEAN
0
QB9 is in open position
QB9_CL
BOOLEAN
0
QB9 is in closed position
QC9_OP
BOOLEAN
0
QC9 is in open position
QC9_CL
BOOLEAN
0
QC9 is in closed position
CQA1_OP
BOOLEAN
0
QA1 in module BH_CONN is in open position
CQA1_CL
BOOLEAN
0
QA1 in module BH_CONN is in closed position
CQB61_OP
BOOLEAN
0
QB61 in module BH_CONN is in open position
CQB61_CL
BOOLEAN
0
QB61 in module BH_CONN is in closed position
CQC1_OP
BOOLEAN
0
QC1 in module BH_CONN is in open position
CQC1_CL
BOOLEAN
0
QC1 in module BH_CONN is in closed position
CQC2_OP
BOOLEAN
0
QC2 in module BH_CONN is in open position
CQC2_CL
BOOLEAN
0
QC2 in module BH_CONN is in closed position
QC11_OP
BOOLEAN
0
Earthing switch QC11 on busbar WA1 is in open
position
QC11_CL
BOOLEAN
0
Earthing switch QC11 on busbar WA1 is in closed
position
VOLT_OFF
BOOLEAN
0
There is no voltage on line and not VT (fuse) failure
VOLT_ON
BOOLEAN
0
There is voltage on the line or there is a VT (fuse)
failure
EXDU_ES
BOOLEAN
0
No transm error from bay containing earthing
switch QC11
QB6_EX1
BOOLEAN
0
External condition for apparatus QB6
QB6_EX2
BOOLEAN
0
External condition for apparatus QB6
QB1_EX1
BOOLEAN
0
External condition for apparatus QB1
QB1_EX2
BOOLEAN
0
External condition for apparatus QB1
QB9_EX1
BOOLEAN
0
External condition for apparatus QB9
Table continues on next page
Section 14
1MRK502052-UEN B
Control
674
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...