Name
Values (Range)
Unit
Step
Default
Description
IL3LowLowLim
0.0 - 500.0
%IB
0.1
60.0
Low Low limit in % of IBase
IL3Min
0.0 - 500.0
%IB
0.1
50.0
Minimum value in % of IBase
IL3LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is
common for all limits
Table 629:
VMMXU Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
UL12DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Operation
Off
On
-
-
Off
Operation Mode On / Off
UL12ZeroDb
0 - 100000
m%
1
1
Zero point clamping
UL12Max
0.0 - 200.0
%UB
0.1
200.0
Maximum value in % of UBase
UL12RepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
UL12AnDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL23DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL2ZeroDb
0 - 100000
m%
1
1
Zero point clamping
UL23Max
0.0 - 200.0
%UB
0.1
200.0
Maximum value in % of UBase
UL23RepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
UL23AnDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL31DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL3ZeroDb
0 - 100000
m%
1
1
Zero point clamping
UL31Max
0.0 - 200.0
%UB
0.1
200.0
Maximum value in % of UBase
UL31RepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
UL31AnDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Table 630:
VMMXU Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
UL12HiHiLim
0.0 - 200.0
%UB
0.1
150.0
High High limit in % of UBase
UL12HiLim
0.0 - 200.0
%UB
0.1
120.0
High limit in % of UBase
UL12LowLim
0.0 - 200.0
%UB
0.1
80.0
Low limit in % of UBase
Table continues on next page
1MRK502052-UEN B
Section 16
Monitoring
869
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...