10.3
Rate-of-change frequency protection SAPFRC
10.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Rate-of-change frequency protection
SAPFRC
df/dt
><
SYMBOL-N V1 EN
81
10.3.2
Functionality
The rate-of-change frequency protection function SAPFRC gives an early indication
of a main disturbance in the system. SAPFRC measures frequency with high
accuracy, and can be used for generation shedding, load shedding and remedial action
schemes. SAPFRC can discriminate between a positive or negative change of
frequency. A definite time delay is provided for operate.
SAPFRC is provided with an undervoltage blocking. The operation is based on
positive sequence voltage measurement and requires two phase-phase or three phase-
neutral voltages to be connected. For information about how to connect analog inputs,
refer to
Application manual/IED application/Analog inputs/Setting guidelines
.
10.3.3
Function block
IEC06000281-2-en.vsd
SAPFRC
U3P*
BLOCK
BLKTRIP
BLKREST
TRIP
START
RESTORE
BLKDMAGN
IEC06000281 V2 EN
Figure 267:
SAPFRC function block
10.3.4
Signals
Table 315:
SAPFRC Input signals
Name
Type
Default
Description
U3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
BLOCK
BOOLEAN
0
Block of function
BLKTRIP
BOOLEAN
0
Blocking operate output
BLKREST
BOOLEAN
0
Blocking restore output
1MRK502052-UEN B
Section 10
Frequency protection
553
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...