Name
Values (Range)
Unit
Step
Default
Description
tTRCrv1
0.005 - 100.000
-
0.001
13.500
Parameter TR for customer
programmable curve for step 1
tCRCrv1
0.1 - 10.0
-
0.1
1.0
Parameter CR for customer
programmable curve for step 1
HarmBlock1
Off
On
-
-
Off
Enable block of step 1 from harmonic
restrain
ResetTypeCrv2
Instantaneous
IEC Reset
ANSI reset
-
-
Instantaneous
Selection of reset curve type for step 2
tReset2
0.000 - 60.000
s
0.001
0.020
Constant reset time for step 2
tPCrv2
0.005 - 3.000
-
0.001
1.000
Parameter P for customer programmable
curve for step 2
tACrv2
0.005 - 200.000
-
0.001
13.500
Parameter A for customer programmable
curve for step 2
tBCrv2
0.00 - 20.00
-
0.01
0.00
Parameter B for customer programmable
curve for step 2
tCCrv2
0.1 - 10.0
-
0.1
1.0
Parameter C for customer programmable
curve for step 2
tPRCrv2
0.005 - 3.000
-
0.001
0.500
Parameter PR for customer
programmable curve for step 2
tTRCrv2
0.005 - 100.000
-
0.001
13.500
Parameter TR for customer
programmable curve for step 2
tCRCrv2
0.1 - 10.0
-
0.1
1.0
Parameter CR for customer
programmable curve for step 2
HarmBlock2
Off
On
-
-
Off
Enable block of step 2 from harmonic
restrain
ResetTypeCrv3
Instantaneous
IEC Reset
ANSI reset
-
-
Instantaneous
Selection of reset curve type for step 3
tReset3
0.000 - 60.000
s
0.001
0.020
Constant reset time for step 3
tPCrv3
0.005 - 3.000
-
0.001
1.000
Parameter P for customer programmable
curve for step 3
tACrv3
0.005 - 200.000
-
0.001
13.500
Parameter A for customer programmable
curve for step 3
tBCrv3
0.00 - 20.00
-
0.01
0.00
Parameter B for customer programmable
curve for step 3
tCCrv3
0.1 - 10.0
-
0.1
1.0
Parameter C for customer programmable
curve for step 3
tPRCrv3
0.005 - 3.000
-
0.001
0.500
Parameter PR for customer
programmable curve for step 3
tTRCrv3
0.005 - 100.000
-
0.001
13.500
Parameter TR for customer
programmable curve for step 3
tCRCrv3
0.1 - 10.0
-
0.1
1.0
Parameter CR for customer
programmable curve for step 3
HarmBlock3
Off
On
-
-
Off
Enable block of step 3 from harmonic
restrain
ResetTypeCrv4
Instantaneous
IEC Reset
ANSI reset
-
-
Instantaneous
Selection of reset curve type for step 4
Table continues on next page
1MRK502052-UEN B
Section 8
Current protection
343
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...