en07000004.vsd
IEC07000004 V1 EN
Figure 108:
Different generator quantities as function of the angle between the
equivalent generators
An alarm is given when movement of the rotor is detected and the rotor angle exceeds
the angle set for 'WarnAngle'.
Slipping is detected when:
•
a change of rotor angle of min. 50 ms is recognized
•
the slip line is crossed between Z
A
and Z
B
.
When the impedance crosses the slip line between Z
B
and Z
C
it counts as being in zone
1 and between Z
C
and Z
A
in zone 2. The entire distance ZA-ZB becomes zone 1 when
signal EXTZONE1 is high (external device detects the direction of the centre of
slipping).
After the first slip, the signals ZONE1 or ZONE2 and – depending on the direction of
slip - either GEN or MOTOR are issued.
Every time pole slipping is detected, the impedance of the point where the slip line is
crossed and the instantaneous slip frequency are displayed as measurements.
Further slips are only detected, if they are in the same direction and if the rate of rotor
movement has reduced in relation to the preceding slip or the slip line is crossed in the
opposite direction outside ZA-ZB. A further slip in the opposite direction within Z
A
-
Z
B
resets all the signals and is then signalled itself as a first slip.
1MRK502052-UEN B
Section 7
Impedance protection
257
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...