Table 456:
DPGAPC Output signals
Name
Type
Description
POSITION
INTEGER
Double point indication
14.7.5
Settings
The function does not have any parameters available in the local HMI or PCM600.
14.7.6
Operation principle
When receiving the input signals, DPGAPC sends the signals over IEC 61850-8-1 to
the systems, equipment or functions that requests and thus subscribes on these signals.
To be able to get the signals into other systems, equipment or functions, one must use
other tools, described in the Engineering manual and define which function block in
which systems, equipment or functions should receive this information.
14.8
Single point generic control 8 signals SPC8GAPC
14.8.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Single point generic control 8 signals
SPC8GAPC
-
-
14.8.2
Functionality
The Single point generic control 8 signals SPC8GAPC function block is a collection
of 8 single point commands that can be used for direct commands for example reset of
LED's or putting IED in "ChangeLock" state from remote. In this way, simple
commands can be sent directly to the IED outputs, without confirmation.
Confirmation (status) of the result of the commands is supposed to be achieved by
other means, such as binary inputs and SPGAPC function blocks. The commands can
be pulsed or steady with a settable pulse time.
1MRK502052-UEN B
Section 14
Control
769
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...