The L_SEL input must be set before L_OPEN or L_CLOSE is
operated, if the control model is Select before operate.
14.3.6.4
Settings
Table 410:
SCSWI Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CtlModel
Dir Norm
SBO Enh
-
-
SBO Enh
Specifies control model type
PosDependent
Always permitted
Not perm at 00/11
-
-
Always permitted
Permission to operate depending on the
position
tSelect
0.00 - 600.00
s
0.01
30.00
Maximum time between select and
execute signals
tResResponse
0.000 - 60.000
s
0.001
5.000
Allowed time from reservation request to
reservation granted
tSynchrocheck
0.00 - 600.00
s
0.01
10.00
Allowed time for synchrocheck to fulfil
close conditions
tSynchronizing
0.00 - 600.00
s
0.01
0.00
Supervision time to get the signal
synchronizing in progress
tExecutionFB
0.00 - 600.00
s
0.01
30.00
Maximum time from command execution
to termination
tPoleDiscord
0.000 - 60.000
s
0.001
2.000
Allowed time to have discrepancy
between the poles
SuppressMidPos
Off
On
-
-
On
Mid-position is suppressed during the
time tIntermediate
InterlockChk
Sel & Op phase
Op phase
-
-
Sel & Op phase
Selection if interlock check should be
done in select phase
14.3.6.5
Operation principle
The Switch controller (SCSWI) is provided with verification checks for the select -
execute sequence, that is, checks the conditions prior each step of the operation are
fulfilled. The involved functions for these condition verifications are interlocking,
reservation, blockings and synchrocheck.
Control handling
.
Two types of control models can be used. The two control models are "direct with
normal security" and "SBO (Select-Before-Operate) with enhanced security". The
parameter
CtlModel
defines which one of the two control models is used. The control
model "direct with normal security" does not require a select whereas, the "SBO with
enhanced security" command model requires a select before execution.
Normal security means that only the command is evaluated and the resulting position
is not supervised. Enhanced security means that the command sequence is supervised
in three steps, the selection, command evaluation and the supervision of position.
Each step ends up with a pulsed signal to indicate that the respective step in the
Section 14
1MRK502052-UEN B
Control
718
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...