Name
Type
Description
CH4
REAL
Analog input 4
CH5
REAL
Analog input 5
CH6
REAL
Analog input 6
21.2.11.4
Settings
Table 915:
MIM Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
On
Operation Off/On
MaxReportT
0 - 3600
s
1
1
Maximum time between reports
EnDeadBandCh1
Off
On
-
-
Off
Enable amplitude deadband reporting for
channel 1
DeadBandCh1
0.00 - 20.00
mA
0.01
1.00
Deadband amplitude for channel 1
IMinCh1
-25.00 - 25.00
mA
0.01
4.00
Min current of transducer for Channel 1
IMaxCh1
-25.00 - 25.00
mA
0.01
20.00
Max current of transducer for Channel 1
ValueMinCh1
-10000000000.000
- 10000000000.000
-
0.001
4.000
Min primary value corr. to IMinCh1
ValueMaxCh1
-10000000000.000
- 10000000000.000
-
0.001
20.000
Max primary value corr. to IMaxCh1
EnDeadBandCh2
Off
On
-
-
Off
Enable amplitude deadband reporting for
channel 2
DeadBandCh2
0.00 - 20.00
mA
0.01
1.00
Deadband amplitude for channel 2
IMinCh2
-25.00 - 25.00
mA
0.01
4.00
Min current of transducer for Channel 2
IMaxCh2
-25.00 - 25.00
mA
0.01
20.00
Max current of transducer for Channel 2
ValueMinCh2
-10000000000.000
- 10000000000.000
-
0.001
4.000
Min primary value corr. to IMinCh2
ValueMaxCh2
-10000000000.000
- 10000000000.000
-
0.001
20.000
Max primary value corr. to IMaxCh2
EnDeadBandCh3
Off
On
-
-
Off
Enable amplitude deadband reporting for
channel 3
DeadBandCh3
0.00 - 20.00
mA
0.01
1.00
Deadband amplitude for channel 3
IMinCh3
-25.00 - 25.00
mA
0.01
4.00
Min current of transducer for Channel 3
IMaxCh3
-25.00 - 25.00
mA
0.01
20.00
Max current of transducer for Channel 3
ValueMinCh3
-10000000000.000
- 10000000000.000
-
0.001
4.000
Min primary value corr. to IMinCh3
ValueMaxCh3
-10000000000.000
- 10000000000.000
-
0.001
20.000
Max primary value corr. to IMaxCh3
EnDeadBandCh4
Off
On
-
-
Off
Enable amplitude deadband reporting for
channel 4
DeadBandCh4
0.00 - 20.00
mA
0.01
1.00
Deadband amplitude for channel 4
IMinCh4
-25.00 - 25.00
mA
0.01
4.00
Min current of transducer for Channel 4
IMaxCh4
-25.00 - 25.00
mA
0.01
20.00
Max current of transducer for Channel 4
Table continues on next page
1MRK502052-UEN B
Section 21
IED hardware
1183
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...