en05000132.vsd
I>
I>
A1
B1
Feeder
Time axis
t=0
t=t
1
t=t
2
t=t
3
IEC05000132 V1 EN
Figure 577:
Selectivity steps for a fault on feeder B1
where:
t=0
is The fault occurs
t=t
1
is Protection B1 trips
t=t
2
is Breaker at B1 opens
t=t
3
is Protection A1 resets
In the case protection B1 shall operate without any intentional delay (instantaneous).
When the fault occurs the protections start to detect the fault current. After the time t
1
the protection B1 send a trip signal to the circuit breaker. The protection A1 starts its
delay timer at the same time, with some deviation in time due to differences between
the two protections. There is a possibility that A1 will start before the trip is sent to the
B1 circuit breaker. At the time t
2
the circuit breaker B1 has opened its primary contacts
and thus the fault current is interrupted. The breaker time (t2 - t1) can differ between
different faults. The maximum opening time can be given from manuals and test
protocols. Still at t
2
the timer of protection A1 is active. At time t
3
the protection A1
is reset, that is the timer is stopped.
In most applications it is required that the times shall reset as fast as possible when the
current fed to the protection drops below the set current level, the reset time shall be
minimized. In some applications it is however beneficial to have some type of delayed
reset time of the overcurrent function. This can be the case in the following
applications:
•
If there is a risk of intermittent faults. If the current IED, close to the faults, starts
and resets there is a risk of unselective trip from other protections in the system.
•
Delayed resetting could give accelerated fault clearance in case of automatic
reclosing to a permanent fault.
•
Overcurrent protection functions are sometimes used as release criterion for other
protection functions. It can often be valuable to have a reset delay to assure the
release function.
1MRK502052-UEN B
Section 25
Inverse time characteristics
1247
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...