Voltage
START
START
TRIP
Start
&
Trip
Output
Logic
Time integrator
Definite Time Delay
tDelay
tReset
Comparator
MinValFreqMeas
BLOCK
IEC05000735-2-en.vsdx
Frequency
Comparator
f > StartFrequency
TRIP
BLKDMAGN
BLOCK
OR
BLKTRIP
IEC05000735 V2 EN
Figure 266:
Simplified logic diagram for SAPTOF
10.2.8
Technical data
Table 314:
SAPTOF technical data
Function
Range or value
Accuracy
Operate value, start function
at symmetrical three-phase
voltage
(35.00-90.00) Hz
± 2.0 mHz
Operate time, start at f
set
-
0.02 Hz to f
set
+ 0.02 Hz
fn = 50Hz
Min. = 80 ms
Max. = 95 ms
-
fn = 60 Hz
Min. = 65 ms
Max. = 80 ms
Reset time, start at f
set
+ 0.02
Hz to f
set
- 0.02 Hz
Min. = 15 ms
Max. = 30 ms
-
Operate time, definite time
function at f
set
-0.02 Hz to f
set
+ 0.02 Hz
(0.000-60.000)s
± 0.2% ± 100 ms
whichever is greater
Reset time, definite time
function at f
set
+ 0.02 Hz to f
set
- 0.02 Hz
(0.000-60.000)s
± 0.2% ± 120 ms,
whichever is greater
Section 10
1MRK502052-UEN B
Frequency protection
552
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...