15.15.4
Signals
Table 608:
TEIGAPC Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Freeze the integration and block the other outputs
IN
BOOLEAN
0
The input signal that is used to measure the
elapsed time, when its value is high
RESET
BOOLEAN
0
Reset the integration time
Table 609:
TEIGAPC Output signals
Name
Type
Description
WARNING
BOOLEAN
Indicator of the integrated time has reached the
warning limit
ALARM
BOOLEAN
Indicator of the integrated time has reached the
alarm limit
OVERFLOW
BOOLEAN
Indicator of the integrated time has reached the
overflow limit
ACCTIME
REAL
Integrated elapsed time in seconds
15.15.5
Settings
Table 610:
TEIGAPC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
tWarning
1.00 - 999999.99
s
0.01
600.00
Time limit for warning supervision
tAlarm
1.00 - 999999.99
s
0.01
1200.00
Time limit for alarm supervision
15.15.6
Operation principle
The elapsed time integrator (TEIGAPC) provides
•
time integration, accumulating the elapsed time when a given binary signal has
been high
•
blocking and reset of the total integrated time
•
supervision of limit transgression and overflow, the overflow limit is fixed to
999999.9 seconds
•
retaining of the integrated value
Figure
describes the simplified logic of the function where the block “Time
Integration“ covers the logics for the first two items listed above while the block
“Transgression Supervision Plus Retain“ contains the logics for the last two.
1MRK502052-UEN B
Section 15
Logic
853
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...