Time Integration
Transgression Supervision
Plus Retain
BLOCK
ACCTIME
RESET
IN
tAlarm
OVERFLOW
WARNING
ALARM
IEC12000195-4-en.vsd
Loop Delay
Loop Delay
tWarning
IEC12000195 V4 EN
Figure 410:
TEIGAPC Simplified logic
TEIGAPC main functionalities
•
integration of the elapsed time when IN has been high
•
applicable to long time integration (≤999 999.9 seconds)
•
output
ACCTIME
presents integrated value in seconds
•
integrated value is retained in nonvolatile memory
•
any retained value with a warning/alarm/overflow is used as initiation
value for the integration following by a restart
•
RESET
: Reset of the integration value. Consequently all other outputs are also
reset
•
unconditionally on the input
IN
value
•
reset the value of the nonvolatile memory to zero
•
BLOCK
: Freeze the integration and block/reset the other outputs
•
unconditionally on the signal value
•
BLOCK
request overrides
RESET
request
•
Monitor and report the conditions of limit transgression
•
overflow if output
ACCTIME
>999999.9 seconds
•
alarm if
ACCTIME
>
tAlarm
•
warning if
ACCTIME
>
tWarning
The
ACCTIME
output represents the integrated time in seconds while
tOverflow
,
tAlarm
and
tWarning
are the time limit parameters in seconds.
tAlarm
and
tWarning
are user settable limits. They are also independent, that is, there
is no check if
tAlarm
>
tWarning
.
Section 15
1MRK502052-UEN B
Logic
854
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...