7.7.6
Monitored data
Table 120:
LEXPDIS Monitored data
Name
Type
Values (Range)
Unit
Description
XOHM
REAL
-
Ohm
Reactance in Primary
Ohms
XPERCENT
REAL
-
%
Reactance in percent of
Zbase
ROHM
REAL
-
Ohm
Resistance in Primary
Ohms
RPERCENT
REAL
-
%
Resistance in percent of
Zbase
7.7.7
Operation principle
The Loss of excitation (LEXPDIS) protection in the IED measures the apparent
impedance seen out from the generator.The measurement loop of apparent impedance
can be chosen as the positive sequence loop or any one of the three phase-to-phase
loops depending on the available current and voltage signals. It is recommended to use
positive sequence quantities for function operation.
Measured mode
Measured apparent impedance
Z
posseq
posseq
posseq
U
I
=
EQUATION1771 V1 EN
(Equation 49)
Z
L1L2
1
2
1
2
L
L
L
L
U
U
I
I
-
=
-
EQUATION1772 V1 EN
(Equation 50)
Z
L2L3
2
3
2
3
L
L
L
L
U
U
I
I
-
=
-
EQUATION1773 V1 EN
(Equation 51)
Z
L3L1
3
1
3
1
L
L
L
L
U
U
I
I
-
=
-
EQUATION1774 V1 EN
(Equation 52)
There are three characteristics in LEXPDIS protection as shown in figure
.
Naimly:
1MRK502052-UEN B
Section 7
Impedance protection
275
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...