0
100
CrvSatn
B
C
×
- >
EQUATION1440 V1 EN
(Equation 121)
The details of the different inverse time characteristics are shown in section
.
TRIP signal issuing requires that the residual overvoltage condition continues for at
least the user set time delay. This time delay is set by the parameter
t1
and
t2
for
definite time mode (DT) and by some special voltage level dependent time curves for
the inverse time mode (IDMT).
If the START condition, with respect to the measured voltage ceases during the delay
time, and is not fulfilled again within a user defined reset time (
tReset1
and
tReset2
for
the definite time and
tIReset1
and
tIReset2
for the inverse time) the corresponding
START output is reset, after that the defined reset time has elapsed.
Here it should be noted that after leaving the hysteresis area, the START condition
must be fulfilled again and it is not sufficient for the signal to only return back to the
hysteresis area. Also notice that for the overvoltage function IDMT reset time is
constant and does not depend on the voltage fluctuations during the drop-off period.
However, there are three ways to reset the timer, either the timer is reset
instantaneously, or the timer value is frozen during the reset time, or the timer value
is linearly decreased during the reset time. See figure
Section 9
1MRK502052-UEN B
Voltage protection
510
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...