In version 2.0, a typical starting time delay of 24ms is subtracted from
the set trip time delay, so that the resulting trip time will take the
internal IED start time into consideration.
25.3
Inverse characteristics
Table 959:
ANSI Inverse time characteristics
Function
Range or value
Accuracy
Operating characteristic:
(
)
1
P
A
t
B k tDef
I
æ
ö
ç
÷
=
+
× +
ç
÷
ç
-
÷
è
ø
EQUATION1249-SMALL V2 EN
Reset characteristic:
( )
2
1
=
×
-
tr
t
k
I
EQUATION1250-SMALL V1 EN
I = I
measured
/I
set
k = (0.05-2.00) in steps of 0.01 ANSI/IEEE C37.112 ,
± 2.0% or ± 40 ms
whichever is greater
ANSI Extremely Inverse
A=28.2, B=0.1217, P=2.0 ,
tr=29.1
ANSI Very inverse
A=19.61, B=0.491, P=2.0 ,
tr=21.6
ANSI Normal Inverse
A=0.0086, B=0.0185, P=0.02,
tr=0.46
ANSI Moderately Inverse
A=0.0515, B=0.1140, P=0.02,
tr=4.85
ANSI Long Time Extremely Inverse
A=64.07, B=0.250, P=2.0,
tr=30
ANSI Long Time Very Inverse
A=28.55, B=0.712, P=2.0,
tr=13.46
ANSI Long Time Inverse
A=0.086, B=0.185, P=0.02,
tr=4.6
1MRK502052-UEN B
Section 25
Inverse time characteristics
1253
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...