1. Current fundamental frequency component >
IMinOpHarmBlk
2. Current second harmonic component >
IMinOpHarmBlk
3. Ratio of the 2nd harmoinc component in relation to the fundamental frequency
component in the residual current exceeds the preset level defined parameter
2ndHarmStab
setting
If all the above three conditions are fulfilled then 2NDHARMD function output signal
is set to logical value one and harmonic restraining feature to the function block is
applicable.
In addition to the basic functionality explained above the 2
nd
harmonic blocking can
be set in such way to seal-in until residual current disappears. This feature might be
required to stabilize EF4PTOC during switching of parallel transformers in the
station. In case of parallel transformers there is a risk of sympathetic inrush current. If
one of the transformers is in operation, and the parallel transformer is switched in, the
asymmetric inrush current of the switched in transformer will cause partial saturation
of the transformer already in service. This is called transferred saturation. The 2
nd
harmonic of the inrush currents of the two transformers is in phase opposition. The
summation of the two currents thus gives a small 2
nd
harmonic current. The residual
fundamental current is however significant. The inrush current of the transformer in
service before the parallel transformer energizing, is a little delayed compared to the
first transformer. Therefore we have high 2
nd
harmonic current component initially.
After a short period this current is however small and the normal 2
nd
harmonic
blocking resets. If the
BlkParTransf
function is activated the 2
nd
harmonic restrain
signal is latched as long as the residual current measured by the relay is larger than a
selected step current level by using setting
UseStartValue
.
This feature has been called Block for Parallel Transformers. This 2
nd
harmonic seal-
in feature is activated when all of the following three conditions are simultaneously
fulfilled:
1. Feature is enabled by entering setting parameter
BlkParTransf
=
On
.
2. Basic 2
nd
harmonic restraint feature has been active for at least 70ms.
3. Residual current magnitude is higher than the set start value for one of the four
residual overcurrent stages. By a parameter setting
UseStartValue
it is possible to
select which one of the four start values that will be used (
IN1>
or
IN2>
or
IN3>
or
IN4>
).
Once Block for Parallel Transformers is activated the basic 2
nd
harmonic blocking
signal is sealed-in until the residual current magnitude falls below a value defined by
parameter setting
UseStartValue
(see condition 3 above).
Simplified logic diagram for 2
nd
harmonic blocking feature is shown in figure
.
Section 8
1MRK502052-UEN B
Current protection
370
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...