8.12.8
Technical data
Table 234:
NS2PTOC technical data
Function
Range or value
Accuracy
Operate current, step 1 - 2
(3-500)% of
IBase
±1.0% of I
r
at I ≤ I
r
±1.0% of I at I > I
r
Reset ratio
>95%
-
Operate time, start at 0 to 2 x I
set
Min. = 15 ms
Max. = 30 ms
-
Reset time, start at 2 to 0 x I
set
Min. = 15 ms
Max. = 30 ms
-
Operate time, start at 0 to 10 x I
set
Min. = 5 ms
Max. = 20 ms
-
Reset time, start at 10 to 0 x I
set
Min. = 20 ms
Max. = 35 ms
-
Time characteristics
Definite or Inverse
-
Inverse time characteristic, step 1 - 2
2
2
I t
K
=
K=1.0-99.0
±2.0% or ±40 ms whichever is
greater
Reset time, inverse characteristic,
step 1 - 2
2
2
I t
K
=
Reset Multiplier = 0.01-20.00
±5.0% or ±40 ms whichever is
greater
Minimum operate time for inverse
time characteristic, step 1 - 2
(0.000-60.000) s
±0.2% or ±35 ms whichever is
greater
Maximum trip delay at 0.5 to 2 x I
set
,
step 1 - 2
(0.00-6000.00) s
±0.2% or ±35 ms whichever is
greater
Independent time delay at 0.5 to 2 x
I
set
, step 1 - 2
(0.00-6000.00) s
±0.2% or ±35 ms whichever is
greater
Independent time delay for Alarm at
0.5 to 2 x I
set
(0.00-6000.00) s
±0.2% or ±35 ms whichever is
greater
8.13
Accidental energizing protection for synchronous
generator AEGPVOC
8.13.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Accidental energizing protection for
synchronous generator
AEGPVOC
U<I>
50AE
Section 8
1MRK502052-UEN B
Current protection
442
Technical manual
Summary of Contents for Relion REG670
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 106: ...100 ...
Page 482: ...476 ...
Page 548: ...542 ...
Page 570: ...564 ...
Page 600: ...594 ...
Page 608: ...602 ...
Page 630: ...624 ...
Page 862: ...856 ...
Page 1094: ...1088 ...
Page 1226: ...1220 ...
Page 1250: ...1244 ...
Page 1297: ...1291 ...