15.10
Controlled emergency stop in inclined elevators
If an emergency stop is implemented in inclined elevators by suddenly closing the brakes, the abrupt
stop can lead to injury to passengers. To avoide this, the cabin should also be braked controlled in
emergency stop.
The
/DELAY
input function is available for this.
When deactivating the input with the
/DELAY
function, the motor is delayed with the delay para-
meterised in the
Controller/A_MAX
menu (see
fi
g.).
Information
At the end of the emergency stop the fault
E208 - DELAY active
is output.
A new run can only be performed after activating the
/DELAY
input function!
RF
V1
V3
RV1/RV2
/DELAY
RB
MB
X-IN
X-OUT
V
t
Controlled emergency stop
RF
Controller enable
V1
Positioning speed
V3
Travel Speed
RV1 / RV2
Direction default
/DELAY
Delay in emergency stop
RB
Controller ready
MB_Brake
Mechanical brake
Original operating instructions
ZETADYN 3C
Special functions
R-TBA08_03-GB 1619
Part.-No. 00163322-GB
183/204
Содержание ZETADYN 3C
Страница 196: ...Original operating instructions ZETADYN 3C EU declaration of conformity R TBA08_03 GB 1619 Part No 00163322 GB 196 204...
Страница 197: ...Original operating instructions ZETADYN 3C EU declaration of conformity R TBA08_03 GB 1619 Part No 00163322 GB 197 204...
Страница 198: ...Original operating instructions ZETADYN 3C EU declaration of conformity R TBA08_03 GB 1619 Part No 00163322 GB 198 204...
Страница 199: ...Original operating instructions ZETADYN 3C EU declaration of conformity R TBA08_03 GB 1619 Part No 00163322 GB 199 204...
Страница 200: ...Original operating instructions ZETADYN 3C EU declaration of conformity R TBA08_03 GB 1619 Part No 00163322 GB 200 204...
Страница 203: ...Original operating instructions ZETADYN 3C R TBA08_03 GB 1619 Part No 00163322 GB 203 204...