Error no.
Error text
Error cause
M S
525
ENC: 1387 ADC Limit
Fault:
signal track A or B of the absolute value or sinus encoder exceeding
permitted limit value during travel
Fault entry not made until end of travel
Travel not cancelled
Remedy:
Check the encoder,
Check the optional PCB for encoder connection,
Check the rotary encoder type in the "Encoder & BC" menu,
●
●
529
Quickstart alarm
Error:
During a quick start function, the machine moves more than 7 mm while
input "V=0" is triggered
Remedy:
Check the parameter in the "Motor name plate" menu,
Shorten time during which input "V=0" is triggered,
check the motor connections (U
R
U; V
R
V; W
R
W)
●
●
535
ZR:RDY abort
Error:
The signal at the digital input set to "ZR_RDY" drops out during travel
Remedy:
Use the ZArec display to check for an error at the ZArec
540
CO: ON!?
Fault:
No signal is available at the end of the contactor monitoring time
T_CDLY
Remedy:
Check the wiring of the contactor monitoring,
check wiring the contactor control
check the power supply of the motor contactors ,
Check the power-supply of the contactor monitoring,
Check contactor switch-on time "T_CDLY " in the "Monitoring" menu,
Check the contactor monitoring in the "Monitoring" menu
Info:
In case of a contactor monitor break, the inputs that triggered the error
are displayed in the "Additional information"
fi
eld (1: CO1, 2: CO2, 3: CO1 and
CO2).
●
544
CO/RF:Vx activ!
Error:
300 ms after switching off the digital outputs RB and MB due to a RF- or
CO-interrupt, the travel comands of the elevator control are still activated
Remedy:
Check the analysis of the output signals from the inverter by the
elevator control
●
545
CO open early
Error:
Motor contactors are open during travel
Remedy:
Check the motor contactor triggering
Check the safety circuit
Info:
In case of a contactor monitor break, the inputs that triggered the error
are displayed in the "Additional information"
fi
eld (1: CO1, 2: CO2, 3: CO1 and
CO2).
●
546
CO: open early M
Error:
Motor contactors are open during travel
Remedy:
Check the motor contactor triggering
Check the safety circuit
●
548
CO1: still on
Error:
5s after expiration of T_CDLY, a signal is still present on the contactor
monitor input CO1
Remedy:
Check the wiring of the contactor monitoring,
check wiring the contactor control
●
549
CO12: still on
Error:
5s after expiration of T_CDLY, a signal is still present on the contactor
monitor input CO1 or CO2
Remedy:
Check the wiring of the contactor monitoring,
check wiring the contactor control
Info:
In case of a contactor monitor break, the inputs that triggered the error
are displayed in the "Additional information"
fi
eld (1: CO1, 2: CO2, 3: CO1 and
CO2).
●
550
MOT: Overload !
Error:
Motor current exceeds the value max for time Tmax
Remedy:
Check the parameter in the "Motor name plate" menu,
Check the weight compensation
Check the brake switching function
●
●
560
V > VZ
Error:
Actual speed exceeds the speci
fi
ed nominal speed for readjustment
when readjusting.
Info:
inverted Function
Error is displayed if entered in mask
At
CONFIG: 31:KL_IO
the function is entered in the mask automatically.
●
Original operating instructions
ZETADYN 3C
Error diagnosis
R-TBA08_03-GB 1619
Part.-No. 00163322-GB
143/204
Содержание ZETADYN 3C
Страница 196: ...Original operating instructions ZETADYN 3C EU declaration of conformity R TBA08_03 GB 1619 Part No 00163322 GB 196 204...
Страница 197: ...Original operating instructions ZETADYN 3C EU declaration of conformity R TBA08_03 GB 1619 Part No 00163322 GB 197 204...
Страница 198: ...Original operating instructions ZETADYN 3C EU declaration of conformity R TBA08_03 GB 1619 Part No 00163322 GB 198 204...
Страница 199: ...Original operating instructions ZETADYN 3C EU declaration of conformity R TBA08_03 GB 1619 Part No 00163322 GB 199 204...
Страница 200: ...Original operating instructions ZETADYN 3C EU declaration of conformity R TBA08_03 GB 1619 Part No 00163322 GB 200 204...
Страница 203: ...Original operating instructions ZETADYN 3C R TBA08_03 GB 1619 Part No 00163322 GB 203 204...