![ZIEHL-ABEGG ZETADYN 3C Скачать руководство пользователя страница 128](http://html1.mh-extra.com/html/ziehl-abegg/zetadyn-3c/zetadyn-3c_original-operating-instructions_3741629128.webp)
(4) Evacuation type default
Con
fi
gure the parameter
F_PARA2 = UPS
in the
Parameter set 2
menu.
Parameter set 2
|
-
"
F_PARA2 UPS
|
-
"
UPS
Function parameter set 2
(5) Presetting the stator resistor in synchronous motors
Con
fi
gure the synchronous motor's stator resistor in the
Parameter set 2 / RS_UPS
menu
Parameter set 2
|
-
"
RS_UPS
1.00
Ohm
|
-
"
1.00
Stator resistance (UPS
(6) Limit motor current
Limit the motor current by entering the available UPS power in the
"Parameter set 2/P_UPS"
menu.
Parameter set 2
|
-
"
P_UPS
1.0
kW
|
-
"
1.0
Max. load of the UPS
Calculating the available UPS power:
x
1 rating plate
- Control systempower consumption
- Electromechanical brakes power consumption
- Other consumers (car light,
…
) power consumption
=
Available UPS_power [W]
Information
Entering the UPS power determines the type of UPS evacuation.
Suf
fi
cient power:
An evacuation trip with the characteristics of an evacuation with optimum UPS
power is implemented.
Not enough power:
An evacuation trip with the characteristics of an evacuation with minimal UPS
power is implemented.
CAUTION!
Caution!
Setting the value for P_UPS too high can lead to an overloading or destruction of the UPS.
(7) Copying the parameters
In the menu
Parameter set 2/COPY
, select the function
PARA->2
. After copying, the parameter is
once again OFF.
Parameter set 2
|
-
"
COPY
Off
|
-
"
PARA1
R
2
Copy parameter
Information
The power failure detection and type of evacuation must be parameterised before copying the
parameters. Only a lower speed of the motor is possible because of the lower mains supply. The
maximum possible speeds for V_2 and V_3 are calculated during the copying process.
Original operating instructions
ZETADYN 3C
Emergency evacuation
R-TBA08_03-GB 1619
Part.-No. 00163322-GB
128/204
Содержание ZETADYN 3C
Страница 196: ...Original operating instructions ZETADYN 3C EU declaration of conformity R TBA08_03 GB 1619 Part No 00163322 GB 196 204...
Страница 197: ...Original operating instructions ZETADYN 3C EU declaration of conformity R TBA08_03 GB 1619 Part No 00163322 GB 197 204...
Страница 198: ...Original operating instructions ZETADYN 3C EU declaration of conformity R TBA08_03 GB 1619 Part No 00163322 GB 198 204...
Страница 199: ...Original operating instructions ZETADYN 3C EU declaration of conformity R TBA08_03 GB 1619 Part No 00163322 GB 199 204...
Страница 200: ...Original operating instructions ZETADYN 3C EU declaration of conformity R TBA08_03 GB 1619 Part No 00163322 GB 200 204...
Страница 203: ...Original operating instructions ZETADYN 3C R TBA08_03 GB 1619 Part No 00163322 GB 203 204...