Emprise 7000 Installation and Service Guide 11
The following figure illustrates how to implement US PDUs with two Emprise 7000 system con-
trollers and four ISE. As shown in the figure, two PDUs are required.
Important
: The following example is for 208V. It is not valid for 120V.
Figure 2-1: US Power Implementation with Two System Controllers and Four ISE at 208V
ISE 1 (3.3A)
Controller Node 0 (2.5A)
ICON (0.5A)
PDU
Storage Fabric Switch (0.5A)
Storage Fabric Switch (0.5A)
PDU
Controller Node 1 (2.5A)
12A max
12A max
12A max
12A max
Do not use
United States: 208V/30A dedicated circuit on site with two 15A circuits in each PDU.
Amps cannot exceed 12 for each circuit (15A derated at 80%).
ISE 2 (3.3A)
ISE 3 (3.3A)
ISE 4 (3.3A)
Ethernet Switch (0.5A)
Ethernet Switch (0.5A)
Ethernet Switch (0.5A)