Emprise 7000 Installation and Service Guide 10
Power Implementation
The Emprise 7000 system controllers and ISE have two power supplies. Xiotech requires the
components of an Emprise storage platform to be plugged into two power distribution units (PDU)
on two separate circuits. You can purchase PDUs directly from Xiotech or through an
independent vendor. Xiotech sells the APC PDU for your convenience.
The United States (US) PDU provides 30A (two circuits with 15A). The derated usage value of
the 15A circuit is 12A (80% of rating). The Outside United States (OUS) PDU provides 20A on
one circuit, or 16A (80% of rating). To verify that the components on a circuit do not add up to
more than the derated value for the PDU you are using, refer to the following table.
The following table lists the operating current for the components of an Emprise storage platform.
Emprise Component
Maximum
Operating Current
200-240V, 50/60 Hz
Maximum
Operating Current
100-125V, 50/60 Hz
Ethernet switch
0.5A
1.0A
Storage-side FC switch
0.5A
1.0A
Ethernet switch
0.5A
1.0A
ICON Appliance (1U)
0.5A
1.0A
System controller
2.5A
5.0A
ISE
3.3A
6.6A
Table 2-1: Emprise 7000 Component Maximum Operating Current