17
Set the signal range of the analogue input
0 = 0-10V / 0-20mA
1 = 2-10V / 4-20mA
18
Set a value for P3.13.1.8 Error Inversion
0 = Normal
1 = Inverted
19
Set a value for P3.13.2.6 Setpoint Source Selection
See table Setpoints in Chapter Table 75 Set-
If you select an analogue input signal, step 20 shows first, and then step 22 shows. With
other selections, the wizard goes to step 21.
If you set Keypad Setpoint 1 or Keypad Setpoint 2 as the value, the wizard goes directly to step
22.
20
Set the signal range of the analogue input
0 = 0-10V / 0-20mA
1 = 2-10V / 4-20mA
21
Set a value for P3.13.2.1 (Keypad Setpoint 1) and
P3.13.2.2 (Keypad Setpoint 2)
Specified by the range set in step 19
22
Use the sleep function
0 = No
1 = Yes
If you give the value Yes in step 22, you see the next 3 steps. If you give the value No, the
wizard goes to step 26.
VACON · 86
WIZARDS