Fault trigger
Autoreset
Trial time
Wait
time
Wait
time
Wait
time
ID717
Reset 1
Reset 2
Trial time
ID718
Fault active
Alarm
Number of trials: (ID759 = 2)
ID717
ID717
Fig. 73: The Automatic reset function
P3.10.6 AUTORESET: UNDERVOLTAGE (ID 720)
Use this parameter to enable the automatic reset after an undervoltage fault.
P3.10.7 AUTORESET: OVERVOLTAGE (ID 721)
Use this parameter to enable the automatic reset after an overvoltage fault.
P3.10.8 AUTORESET: OVERCURRENT (ID 722)
Use this parameter to enable the automatic reset after an overcurrent fault.
P3.10.9 AUTORESET: AI LOW (ID 723)
Use this parameter to enable the automatic reset after a fault caused by low AI signal.
P3.10.10 AUTORESET: UNIT OVERTEMPERATURE (ID 724)
Use this parameter to enable the automatic reset after a fault caused by unit
overtemperature.
P3.10.11 AUTORESET: MOTOR OVERTEMPERATURE (ID 725)
Use this parameter to enable the automatic reset after a fault caused by motor
overtemperature.
PARAMETER DESCRIPTIONS
VACON · 297