1
6
2
3
4
5
18
19
30
12
7
13
8
9
10
14
15
16
21
22
23
11
17
A
B
24
25
26
28
29
32
33
Modbus RTU
+
-
*)
**)
mA
FAULT
RUN
RUN
AO1-/GND
+24 Vin
24 V out
GND
GND
DI1
DI2
DI3
DI4
DI5
DI6
CM
CM
RS485
RS485
Standard I/O board
Terminal
Signal
Description
+10Vref
AI1+
AI1-
AI2+
AI2-
24Vout
Reference output
Analogue input 1 +
Analogue input 1 -
Analogue input 2 +
Analogue input 2 -
24V auxiliary voltage
I/O ground
Digital input 1
Digital input 2
Digital input 3
Digital input 4
Digital input 5
Digital input 6
Common for DI1-DI6
Common for DI1-DI6
24V auxiliary voltage
I/O ground
Analogue output 1 +
Analogue output 1 -
24V auxiliary
input voltage
Output
frequency
0...20mA)
Serial bus, negative
Serial bus, positive
Relay output 1
Relay output 2
READY
Relay output 3
Thermistor input
FAULT
Fault reset
AO1+
Place A: PID setpoint
(reference)
Place B: Frequency
reference
(default: 0...10V)
PID feedback
(actual value)
(default: 4...20mA)
Place A: Start forward
(PID controller)
External fault
Control place A/B selection
Reference-
potentiom-
eter
1...10kΩ
Preset frequency 1
I =
(0)4...20mA
Actual
value
2-wire
transmitter
Place B: Start forward
(Freq. reference P3.3.1.6)
RO3/3 NO
RO3/2 CM
TI1-
TI1+
RO2/3 NO
RO2/2 CM
RO2/1 NC
RO1/1 NC
RO1/2 CM
RO1/3 NO
Fig. 6: The default control connections of the PID control application
* = Available only in VACON
®
100 X.
QUICK STARTUP GUIDE
VACON · 23
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
1
Содержание 100 flow
Страница 1: ...vacon 100 flow ac drives application manual ...
Страница 2: ......
Страница 6: ...VACON 6 LOCAL CONTACTS HTTP DRIVES DANFOSS COM DANFOSS DRIVES LOCAL CONTACTS ...