Table 12: M1 Quick setup
Index
Parameter
Min
Max
Unit
Default
ID
Description
1.18
Automatic
Reset
0
1
0
731
0 = Disabled
1 = Enabled
1.19
Response to
External
Fault
0
3
2
701
0 = No action
1 = Alarm
2 = Fault (Stop
according to stop
mode)
3 = Fault (Stop by
coasting)
1.20
Response to
AI Low Fault
0
5
0
700
0 = No action
1 = Alarm
2 = Alarm+preset
fault frequency
(P3.9.1.13)
3 = Alarm + previous
frequency
4 = Fault (stop
according to stop
mode)
5 = Fault (stop by
coasting)
1.21
Remote
Control
Place
0
1
0
172
The selection of the
remote control place
(start/stop).
0 = I/O control
1 = Fieldbus control
VACON · 70
QUICK STARTUP GUIDE
1
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/