Table 13: M1.35 Multi-pump (Multidrive)
Index
Parameter
Min
Max
Unit
Default
ID
Description
1.35.16
Start and Feed-
back Signals
0
2
1
1782
Use this parameter
to select if the start
signal and/or the
PIDfeedback sig-
nals are connected
to the drive.
0 = Not connected
1 = Only Start Sig-
nal Connected
2 = Both Signals
Connected
1.35.17
Pump Interlock-
ing
0
1
1
1032
Enable/Disable
interlocks. Inter-
locks tell the sys-
tem if a motor is
connected or not.
0 = Disabled
1 = Enabled
1.35.18
Autochange
0
2
1
1027
Disable/enable the
rotation of the start
order and the pri-
ority of the motors.
0 = Disabled
1 = Enabled (inter-
val)
2 = Enabled (week-
days)
1.35.19
Autochanged
Pump
0
1
1
1028
0 = Auxiliary Pump
1 = All Pumps
1.35.20
Autochange
Interval
0.0
3000.0
h
48.0
1029
When the time
specified by the
this parameter is
used, the autoch-
ange function
starts. But the
autochange starts
only if the capacity
is below the level
specified by
parameters
P1.35.23 and
P1.35.24.
QUICK STARTUP GUIDE
VACON · 75