5.20
GROUP 3.21: PUMP CONTROL
Table 98: Auto-cleaning parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.21.1.1
Cleaning Function
0
3
0
1714
0 = Disabled
1 = Enabled (DIN)
2 = Enabled (current)
3 = Enabled (weekdays)
P3.21.1.2
Cleaning Activation
DigIN
Slot0.1
1715
P3.21.1.3
Cleaning Current
Limit
0.0
200.0
%
120.0
1712
P3.21.1.4
Cleaning Current
Delay
0.0
300.0
s
60.0
1713
P3.21.1.5
Cleaning Weekdays
0
127
0
1723
B0 = Sunday
B1 = Monday
B2 = Tuesday
B3 = Wednesday
B4 = Thursday
B5 = Friday
B6 = Saturday
P3.21.1.6 Cleaning Time of Day 00:00:00 23:59:59
00:00:00
1700
P3.21.1.7
Cleaning Cycles
1
100
5
1716
P3.21.1.8
Clean Forward Fre-
quency
0.00
50.00
Hz
45.00
1717
P3.21.1.9
Clean Forward Time
0.00
320.00
s
2.00
1718
P3.21.1.1
0
Clean Reverse Fre-
quency
0.00
50.00
Hz
45.00
1719
P3.21.1.1
1
Clean Reverse Time
0.00
320.00
s
0.00
1720
P3.21.1.1
2
Cleaning Accelera-
tion Time
0.1
300.0
s
0.1
1721
P3.21.1.1
3
Cleaning Decelera-
tion Time
0.1
300.0
s
0.1
1722