Table 79: Feedback supervision parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.13.6.1
Enable Feedback
Supervision
0
1
0
735
0 = Disabled
1 = Enabled
P3.13.6.2
Upper Limit
-99999.9
9
99999.9
9
Varies
Varies
736
P3.13.6.3
Lower Limit
-99999.9
9
99999.9
9
Varies
Varies
758
P3.13.6.4
Delay
0
30000
s
0
737
P3.13.6.5
Response to PID
Supervision Fault
0
3
2
749
0 = No action
1 = Alarm
2 = Fault (Stop accord-
ing to stop mode)
3 = Fault (Stop by
coasting)
Table 80: Pressure loss compensation parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.13.7.1
Enable Setpoint 1
0
1
0
1189
0 = Disabled
1 = Enabled
P3.13.7.2 Setpoint 1 Max Com-
pensation
-99999.9
9
99999.9
9
Varies
0.00
1190
P3.13.7.3
Enable Setpoint 2
0
1
0
1191
See P3.13.7.1.
P3.13.7.4 Setpoint 2 Max Com-
pensation
-99999.9
9
99999.9
9
Varies
0.00
1192
See P3.13.7.2.
PARAMETERS MENU
VACON · 169
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/