Table 13: M1.35 Multi-pump (Multidrive)
Index
Parameter
Min
Max
Unit
Default
ID
Description
1.35.21
Autochange Days
0
127
1786
Range: Monday to
Sunday
1.35.22
Autochange Time
of Day
Time
1787
Range: 00:00:00 to
23:59:59
1.35.23
Autochange:
Frequency Limit
0.00
P3.3.1.2
Hz
25:00
1031
These parameters
set the level below
which the capacity
must stay for the
autochange to
start.
1.35.24
Autochange:
Pump Limit
1
6
1030
1.35.25
Bandwidth
0
100
%
10
1097
When the feedback
value stays
between 4.5 and .
5.5 bar, the motor
stays connected.
Setpoint = 5 bar
Bandwidth = 10%
When the feedback
value stays
between 4.5 and
5.5 bar, the motor
stays connected.
1.35.26
Bandwidth Delay
0
3600
s
10
1098
When the feedback
is outside the
bandwidth, the
time after which
pumps are added
or removed.
1.35.27
Constant Pro-
duction Speed
0
100
%
100
1513
Gives the constant
speed at which the
pump locks, when
the pump goes to
the maximum fre-
quency. The next
pump starts the
regulation in the
multimaster mode.
1.35.28
Pump 1 Interlock
DigIN
Slot0.1
426
OPEN = Not active
CLOSED = Active
1.35.29
Flushing Refer-
ence
Maximum
reference
Maximum
reference
HZ
50.00
1239
Gives the frequency
reference when the
flush function is
activated.
VACON · 76
QUICK STARTUP GUIDE
1
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/