Table 51: Standard I/O board analogue output settings, Slot A
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.5.4.1.1
AO1 function
0
31
2 *
10050
17 = ProcessDataIn4
(0-100%)
18 = ProcessDataIn5
(0-100%)
19 = ProcessDataIn6
(0-100%)
20 = ProcessDataIn7
(0-100%)
21 = ProcessDataIn8
(0-100%)
22 = Block Out.1
(0-100%)
23 = Block Out.2
(0-100%)
24 = Block Out.3
(0-100%)
25 = Block Out.4
(0-100%)
26 = Block Out.5
(0-100%)
27 = Block Out.6
(0-100%)
28 = Block Out.7
(0-100%)
29 = Block Out.8
(0-100%)
30 = Block Out.9
(0-100%)
31 = Block Out.10
(0-100%)
P3.5.4.1.2
AO1 filter time
0.0
300.0
s
1.0 *
10051 0 = No filtering
P3.5.4.1.3
AO1 minimum
0
1
0 *
10052 0 = 0 mA / 0V
1 = 4 mA / 2V
P3.5.4.1.4 AO1 minimum scale -214748.
36
214748.
36
Varies
0.0 *
10053
P3.5.4.1.5 AO1 maximum scale -214748.
36Varies
214748.
36
Varies
0.0 *
10054
* = The selection of the application with parameter P1.2 Application gives the default value.
See the default values in 12.1 The default values of parameters in the different applications.
THE ANALOGUE OUTPUTS OF THE EXPANDER SLOTS C, D AND E
Shows only the parameters for the outputs on option boards in slots C, D and E. Make the
selections as in AO1 Function (P3.5.4.1.1).
This group or these parameters do not show, if there are no digital outputs in slots C, D or E.
VACON · 148
PARAMETERS MENU
5
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/