5.3
GROUP 3.3: REFERENCES
Table 34: Frequency reference parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.3.1.1
Minimum Frequency
Reference
0.00
P3.3.1.2
Hz
0.00
101
P3.3.1.2
Maximum Frequency
Reference
P3.3.1.1
320.00
Hz
50.00 /
60.00
102
P3.3.1.3
Positive Frequency
Reference Limit
-320.0
320.0
Hz
320.00
1285
P3.3.1.4
Negative Frequency
Reference Limit
-320.0
320.0
Hz
-320.00
1286
P3.3.1.5
I/O Control Refer-
ence A Selection
0
20
6 *
117
0 = PC
1 = Preset frequency 0
2 = Keypad reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID
8 = Motor potentiome-
ter
11 = Block Out.1
12 = Block Out.2
13 = Block Out.3
14 = Block Out.4
15 = Block Out.5
16 = Block Out.6
17 = Block Out.7
18 = Block Out.8
19 = Block Out.9
20 = Block Out.10
P3.3.1.6
I/O Control Refer-
ence B Selection
0
20
4 *
131
PARAMETERS MENU
VACON · 133
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
5
Содержание 100 flow
Страница 1: ...vacon 100 flow ac drives application manual ...
Страница 2: ......
Страница 6: ...VACON 6 LOCAL CONTACTS HTTP DRIVES DANFOSS COM DANFOSS DRIVES LOCAL CONTACTS ...